ArmaProtect FC2
Firestop collar for fire seals in walls and floors
Technical information ArmaProtect FC2
Material type
Powder-coated sheet steel housing (Ø up to 200mm)
Special features
- Easy visual inspection.
Property | Value / Assessment | Standard / Test method |
---|---|---|
Operating temperature | ||
Operating temperature | -40°C to 70°C (40°F to 158°F) | |
Processing Temperature | ||
Processing temperature | 5°C to 25°C (41°F to 77°F) | |
Fire Performance and Approvals | ||
Reaction to fire | Housing: Class A1
Inlay: Class E | EN 13501-1 |
Use category | Type X: intended for use in conditions exposed to weathering | EOTA TR 024 |
Passive fire protection | ||
Fire resistance of elements of construction | Drywall, concrete wall, aerated concrete wall, masonry wall, concrete floors: up to EI 120 | EN 13501-2 |
Physical attributes | ||
Thickness | 1,0 mm up to 8,0 mm | EOTA TR 024 |
Density | 1200 kg/m³ ± 10 % | EOTA TR 024 |
Mechanical properties | ||
Expansion ratio | Inlay: 18 to 38 times | EOTA TR 024 |
Health and environment | ||
Health aspects | Please refer to the safety data sheet available on our website. | |
Emission of dangerous substances | No dangerous substances. | |
Other technical features | ||
Storage | Store / Transport in a cool and dry place with an ambient temperature of 5 °C to 25 °C (41°F to 77°F) and protect from frost. |