ArmaProtect CB
Ablative coated board system for mixed fire seals in walls and floors
Technical information ArmaProtect CB
Material type
Mineral wool board with ablative firestop coating and ablative firestop filler mastic.
Additional material information
- The entire system as well as the separate components (coated board, ablative firestop coating and ablative firestop filler mastic) are halogen- and solvent-free.
Special features
- In a cured state, the ablative firestop coating (ArmaProtect ABLC) and ablative firestop filler mastic (ArmaProtect ABLF) are resistant against humidity, frost-dew-change and UV radiation.
Property | Value / Assessment | Standard / Test method |
---|---|---|
Operating temperature | ||
Operating temperature | -40°C to +70°C (-40°F to 158°F) | |
Processing Temperature | ||
Processing temperature | 5°C to 25°C (41°F to 77°F) | |
Fire Performance and Approvals | ||
Reaction to fire | Class E | EN 13501-1 |
Use category | Type X: intended for use in conditions exposed to weathering | EOTA TR 024 |
Passive fire protection | ||
Fire resistance of structural element | Concrete wall, aerated concrete wall, masonry wall, concrete floor: up to EI 240
UL approved system: FT-Rating - up to 3 hours | ANSI/UL 1479 (ASTM E814), EN 13501-2 |
Physical attributes | ||
Density | ArmaProtect ABLC Firestop coating: 1.34 - 1.48 g/cm³ (at 20 °C)
ArmaProtect ABLF Firestop filler mastic: 1.34 - 1.48 g/cm³ (at 20 °C) | |
Health and environment | ||
Volatile organic compounds (VOC) content | ArmaProtect ABLC Firestop coating: < 50 g/l
ArmaProtect ABLF Firestop filler mastic: < 50 g/l | GS-11, Green Seal Standard |
Health aspects | Please refer to the safety data sheet available on our website. | |
Emission of dangerous substances | No dangerous substances. | |
Other technical features | ||
Cure time | Dust-dry: > 4 h (23 °C / 65% relative humidity)
2nd layer: > 8 h (23 °C / 65% relative humidity) Fully cured: > 4 d (23 °C / 65% relative humidity) | EOTA TR 024 |
Shelf life1 | Can be kept for at least 18 months if unopened and stored properly. | |
Storage | ArmaProtect CB Coated firestop board: 5°C to 25°C (41°F to 77°F)
ArmaProtect ABLC Firestop coating; 5°C to 25°C (41°F to 77°F) ArmaProtect ABLF Firestop filler mastic: 5°C to 25°C (41°F to 77°F) Store / Transport in a cool and dry place and protect from frost. | |
1ArmaProtect ABLC Firestop coating and ArmaProtect ABLF Firestop filler mastic only. |