Product_Header_1920x384_ArmaProtect

ArmaProtect FC1

Firestop collar for fire seals in walls and floors

Technical information ArmaProtect FC1
Product_pdpImage-800x800_ArmaProtect_FC1

Material type

  • Galvanised sheet steel housing with flexible intum

Special features

  • Easy visual inspection.
PropertyValue / AssessmentStandard / Test method
Operating temperature
Operating temperature-40°C to 70°C (40°F to 158°F)
Processing Temperature
Processing temperature5°C to 25°C (41°F to 77°F)
Fire Performance and Approvals
Reaction to fireHousing: Class A1
Inlay: Class E
EN 13501-1
Use categoryType Y1: intended for use at temperatures below 0°C with exposure to UV but no exposure to rainEOTA TR 024
Passive fire protection
Fire resistance of elements of construction1Drywall, concrete wall, aerated concrete wall, masonry wall: up to EI 120
Concrete floors: up to EI 240
EN 13501-2
Physical attributes
Thickness2 mm ± 0,2mm (sheets)EOTA TR 024
DensityInlay: 1.02 -1.42 g/cm³ (thickness 2 mm)EOTA TR 024
Mechanical properties
Expansion pressureInlay: > 0.6 N/mm² EOTA TR 024
Weight loss on heatingInlay: 52 - 62% (at 550°C, 30 minutes)EOTA TR 024
Expansion ratioInlay: 12 - 22.5 timesEOTA TR 024
Health and environment
Health aspectsPlease refer to the safety data sheet available on our website.
Emission of dangerous substancesNo dangerous substances.
Other technical features
StorageStore / Transport in a cool and dry place with an ambient temperature of 5 °C to 25 °C (41°F to 77°F) and protect from frost.

1See ETA 21/1024 for further installation details.