Armacell - Wind Chill Factor /

Wind Chill Factor
For an insulated surface, movement of air over that surface has only a small effect on the overall heat loss but will reduce the temperature of the insulated surface. The effect of air movement is to increase the convection component of the surface coefficient.

Consider the following example:
  • Ambient = 20°C
  • Line = 80°C
  • l Value = 0.039 W/(m.K)
  • Pipe diameter = 42 mm
  • Insulation thickness = 19 mm
We may calculate the heat loss in still air (natural convection) and moving air:
Still
Moving
Values of h in W/m2.K9.039.0
heat loss in W/m19.922.4
Surface temperature in °C28.820.2

Date of Release:

All data is valid for the application of our products in United Kingdom, Ireland and South Africa. If you want to apply our products in other countries, please call our customer service. All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient.