Armacell - Ductwork /

Ductwork

Ducts are used either for warm air heating or air conditioning.


Warm Air

Insulate for energy conservation in accordance with the Building Regulations, Approved Document L1.

1.39 Unless the heat loss from a pipe or duct contributes to the useful heat requirement of a room or space the pipe or duct shall be insulated.

The requirement would be satisfied for warm air ducts and in the case of pipes if insulation is provided in accordance with the recommendations of BS 5422:1990 table 16

Temperature difference between ambient and air inside duct
10 K
25 K
50 K
Class O Armaflex
32
38
50
NH/Armaflex
38
44
63
HT/Armaflex
38
44
63

These Armaflex thickness recommendations are in broad agreement with the insulated heat loss values quoted in BS 5422:1990 Table 16 “Economic thickness of insulation on ductwork carrying warm air”.


Air Conditioning

Insulate for condensation control, as a minimum requirement. Additional insulation thickness may be desirable to reduce heat gain.


Chilled Air in Warm Space

Minimum commercially available thicknesses of Class O Armaflex and NH/Armaflex insulation for

condensation control on ductwork carrying chilled air.

Ambient conditions
Insulation
Air temperature inside duct
Temp.
Rel. humidity
15 °C
10 °C
5 °C
0 °C
25 °C
80%
Class O Armaflex
6 mm
13 mm
19 mm
25 mm
NH/Armaflex
9 mm
19 mm
25 mm
25 mm
HT/Armaflex
9 mm
19 mm
25 mm
25 mm
20 °C
70%
Class O Armaflex
6 mm
6 mm
6 mm
13 mm
NH/Armaflex
6 mm
6 mm
9 mm
13 mm
HT/Armaflex
6 mm
6 mm
9 mm
13 mm

Air temperature 25 ºC and relative humidity 80% are the ambient conditions used in the calculation of Table 16 in BS 5422 : 1990 for a material with high emissivity.


Vapour barrier

For chilled air ductwork it is a technical requirement that a vapour barrier shall be applied on the exposed face. The permeance shall not exceed 0.05 g/(s.MN). All Armaflex thermal insulation materials exceed this requirement at the thickness shown above.
Related information:
Specification Form - Ductwork
Date of Release: print friendly page

All data is valid for the application of our products in United Kingdom, Ireland and South Africa. If you want to apply our products in other countries, please call our customer service. All statements and technical information are based on results obtained under typical conditions. It is the responsibility of the recipient to verify with us that the information is appropriate for the specific use intended by the recipient.